• <mark id="tvakd"></mark>

          <label id="tvakd"></label>
        1. <tt id="tvakd"></tt>

        2. Product--CP15KVA

          • Product Name: CP15KVA
          • Product Category: Low Frequency Online UPS
          • Power Range: 1200W
          • Work: one in one out /three in one out low frequency online
          • Applications: Small and medium size data centre, industrial automation device, Network Computer System, intelligent precision instrument products & key equipment, Network Management Center, etc
          • Product Viewed: 16783

          CP15KVA - Other Explain

          Basic Features

          1.True Online UPS, pure sine wave output, application of Double Conversion IGBT module technical achievement, displayed a small volumn, low noise operation, good durability;

          2.LCD panel: read the UPS operation status(parameters) by clicking the optional switch on the panel conveniently: whether the internal or external battery in a normal status(DC Voltage), voltage value(Input & Output),frequency value(Input & Output), loaded power value and so on;

          3.Wide I/P Voltage range, UPS could be full-loaded in a 25% tolerance, reducing battery-discharging rate greatly, so, the battery’s life-span be extended remarkably;

          4.1AMP to 10AMP battery charging current offer a good solution for the battery in any long backup UPS which is very popular in the area with bad power situation;

          5.Special design on Static power switch makes UPS stop output upon any mains input problem, and when UPS fails, transfer time to bypass witin two seconds;

          6.Good load ability, when over-loading to 125%, bypass operates automatically after one minute, UPS outupt will return after over-load passes;

          7.Short-circuit protection provent the UPS from any damage caused by the load short-circuit problem;

          8.Temperature controlling: design the internal temperature automatically, prevent the internal components from burning;

          9.Good loading ability: UPS could be switched on battery status and then output for equipments connected;

          10.Isolation transformer isolates input and output completely, free from any interference, UPS operates in a safe mode;

          11.Redundant and parallel design;

          12.Alarming device remind the vendors caring UPS working status;

          13.RS232 & SNMP communication port make the UPS management and control locally and remotely;

          14.More capacity choice from 1KVA to 30KVA(1-20KVA be 1/1 phasic I/P and O/P), and (10-30KVA optional to 3/1 phasic configuration).

           

          Technical parameter for CP series

           

          Model

          CP1KVA

          CP2KVA

          CP3KVA

          CP4KVA

          CP6KVA

          CP8KVA

          CP10KVA

          CP15KVA

          CP20KVA

          CP30KVA

          Capacity

          0.8KW

          1.6KW

          2.4KW

          3.2KW

          4.8KW

          6.4KW

          8KW

          12KW

          16KW

          24KW

          Input Voltage

          1 phase 220VAC ± 25%               3 phase 380VAC ± 25%

          Input Frequency

          50HZ or 60HZ ± 5%

          Output Voltage

          220VAC ± (1- 5%) (adjustable)

          Output Frequency

          50HZ ± 5%

          Voltage Tolerance

          ±2%

          Transient Response

          ±4% (100% load)

          Wave Form

          Sine wave THD < 3%          0~100% (linear load)

          Overload Capacity

          120~150% for 60 sec >150% (constant power)

          Power Factor

          0.8~1, Lagging

          Crest Factor

          3:1

          Battery Type

          maintenance free sealed lead acid battery

          DC Voltage

          48VDC

          96VDC

          192VDC

          Charger

          1~10A (adjustable)

          Efficiency

          ≥85%

          Transfer Time

          Zero

          Protection

          Input overcurrent, breaker, overload, overheat, bypass

          EMI Filter

          10~100KHZ in 40dB, 100KHZ~100MHZ in 70dB

          Auto alarm utility failure

          Alarm every 4 seconds for 90 mins

          Low Battery

          Alarm every 1 second (auto shutdown & restart)

          Overload

          Continuous buzzer for 60 sec then bypass

          Fault

          Continuous buzzer

          LED Display

          AC input/bypass/inverter/battery overload

          LCD Display

          Input/output/battery voltage, input/output frequency, load percentage, UPS status

          Interface

          AC fault, low battery, bypass inverter, remote intelligent software

          Temperature

          0~40 ‘C

          Physical Dimension(mm)

          525*170*390

          587*212*420

          580*230*580

          480*340*825

          750*410*1100

          (D*W*H)

          1K

          2K

          3K

          4K

          6K

          8K

          10K

          15K

          20K

          30K

          N. Weight (KG)

          18.5

          35

          43

          52

          65

          70

          80

          210

          250

          280

          Humidity

          20~90% (non-condensing, max)

          Noise

          58dB (within a distance of 1 meter)